XP 1100 SINE WAVE INVERTER

12-108 VDC INPUT 100, 120 or 230 VAC OUTPUT @ 1100W

50, 60, or 400Hz available

Designed to operate in mobile & extreme rugged environments

UL Listed to 1950 for Telecom applications

EXELTECH, Inc.

 

 

 

 

 

 

 

 

 

 

 

 

Model No.

0/P Designation

Output Voltages

I/P Designation

Input Voltages

Freq. Designation

Frequencies

Option Designation

Options

 

 

 

 

 

 

 

 

 

 

 

 

 

XP 1100

0

100 VAC

1

12 VDC

5

50 Hz

07

Conformal Coat

 

 

 

1

120 VAC

2

24 VDC

6

60 Hz

04

Circuit Board w / heat sink**

 

 

 

3

 230 VAC

B

32 VDC

4

400 Hz

 

 

 

 

 

 

 

4

48 VDC

 

 

 

 

 

 

 

 

 

E

66 VDC

 

 

 

 

 

 

 

 

 

I

108 VDC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

** OEM ONLY

 

 

 

 

 

 

 

 

 

 

 

 

 

To create part number pick designation. Example below is XP1100, 100 VAC output, 24 VDC input, 60 Hz, Conformal Coated

 

 

XPK

0

 

2

 

6

 

07

 

 

 

 

 

 

 

 

 

 

 

 

 

 

XPK-___-___-___-1-____

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OUTPUT POWER

 

 

 

Continuous Power

Surge Power

No Load Power

Output Voltage

Output Current

Weight Lbs

Mechanical

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1100W

2200W

20W*

100 +/-6%

11

10

3.57" X 7.69" X 15.05"

 

 

 

1100W

2200W

20W*

117 +/-6%

9.5

10

3.57" X 7.69" X 15.05"

 

 

 

1100W

2200W

20W*

230 +/-6%

4.8

10

3.57" X 7.69" X 15.05"

 

 

 

*  10W w/ X2 option

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INPUT POWER

 

PROTECTION CIRCUITRY

 

 

Input Voltage

Minimum¹ Voltage (Typical)

System Voltage (Typical)

Maximum¹ Voltage (Typical)

Typical Efficiency @ Full Power

Peak Efficiency @ 1/3 power

 

*OVP

Shut off at maximum input voltage, per input conditions. Automatic reset upon fault correction

 

 

 

 

 

 

 

 

 

*Under Voltage

Shutoff at minimum input voltage, per input conditions

 

 

12VDC

10.4/10.6*

13.8

16.5

85

87

 

 

 

 

 

24VDC

19/21*

27.6

33

87

89

 

*Thermal

105 C internal temperature. Warning buzzer 5 C before shutoff

 

 

32VDC

26.5/28*

36.8

44

88

90

 

 

 

 

 

48VDC

41.5/42.5

55.2

62

87

89

 

Output Short

Unit shuts off(manual reset)

 

 

66VDC

57.5/58.5*

75.9

91

88

90

 

*Automatically reset

 

 

108VDC

94/95*

125

149

87

90

 

 

 

 

 

*Indicates typical cut-off voltage/warning buzzer voltage

 

 

 

 

 

¹  +/-3%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GENERAL

 

ENVIRONMENTAL

 

 

 

Conditions

Minimum

Typical

Maximum

 

Temperature

     -25 to 30C full power

 

 

 

Waveform

-

SINUSOIDAL

-

 

 

     derated above 30 C

 

 

 

Voltage Output

-5%

NOMINAL

+5%

 

 

 

 

 

 

 

Line regulatiion

-

0.10%

0.50%

 

Humidity

     5 to 95% non condensing

 

 

 

Load Regulation

 

0.50%

1%

 

 

 

 

 

 

 

Distortion

-